Description
The room hygrostat serves for the supervision and control of the relative humidity e.g. in business premises, domiciles, habitations, conservatories, bathing rooms, swimming pools, EDP rooms.
| Technical Data | |
| Operating Voltage: | 24…230 V ~ |
| Sensor: | Synthetic fibres |
| Switching Capacity: | At 230 V ~ for dry rooms only and
24 ~ |
| Dehumidifying: | 5 (0.2) A |
| Humidifying: | 3 (0.2) A FHY: 2 (0.2) A |
| Contact: | Changeover contact |
| Min. Switching Current: | Min. 100 mA @ 24 V ~ |
| Setting Ranges: | 30…100% r.h./FHY: 35…85% r.h. |
| Switching Difference: | Approx. 4% r.h./
FHY: approx. 5% r.h. |
| Measuring Accuracy: | Approx. 3% r.h.
(Micro switch at 50% r.h.) FHY: approx. 4% r.h. (Micro switch at 50% r.h.) |
| Degree of Protection: | IP 30 |
| Protection Class: | II, after according installation |
| General Equipment: | Mechanical range reduction |
| Admissible Humidity: | Max. 95% r.h., non-condensing |
| Storage Temperature: | -20…+60°C |
| Safety and EMC: | According to DIN EN 60730 |
| Ambient Temperature: | 0…60°C, FHY + RKDSB: 0…50°C |
| Housing Colour: | Pure white, similar to RAL 9010 |




Reviews
There are no reviews yet.