Description
Control and supervision of temperatures in closed, dry rooms. Suited for all types of heating systems. Valve: normally closed type. Normally open heating valves must, if existing, be connected to the cooling outlet of the changeover contact., e.g. FTR 101
Cover sets are offered in various designs and are not included in the delivery. Atricle no. of suitable sets JZ-001.xxx e.g.
Cover set 50 x 50 mm, pure white, glossy, JZ-001.000
Cover set 55 x 55 mm, pure white, glossy, JZ-001.100 PG: I
Technical Data | |
Operating Voltage: | 230 v ~, 50 Hz |
Sensor: | Bimetal |
Switching Capacity bei 230 V AC:
Break Contact Umschalter (Wechsler) |
10 (4) A, VDE see circuit diagram 5 (2) A, VDE see circuit diagram |
At 24 V AC: | 1 (1) A |
Setting Ranges: | 5…30°C (numeric scale *…6) |
Switching Difference: | Approx. 0,5 K with a temperature change of max. 4 K/h |
Temperature Decrease: | Approx. 4 K |
Degree of Protection: | IP 30 |
Protection Class: | I, after installation
At 24 V ~ protection class III |
General Equipment: | Thermal feedback,
Mechanical range reduction, |
Admissible Air Moisture: | Max. 95% r.h., non-condensing |
Storage Temperature: | -20…+70°C |
Safety and EMC: | Acc. to DIN EN 6073. |
Ambient Temperature: | 0…30°C |
Housing Colour: | Available in several variants to match selected cover |
Housing Material: | Polycarbonate (PC) |
Mounting/Installation | In a flush-mounting box with
50 x 50mm or 55 x 55mm cover, can be adapted to almost all flush-mounted switch ranges |